Final | 12/4/2018 | 12/5/2018 | 12/5/2018 | A | PASS |
Tom Saunders
|
|
|
Corbin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg....ok to final
|
Electrical Rough-In | 9/27/2018 | 9/28/2018 | 9/28/2018 | A | PASS |
Rock A. Hudson
|
|
|
David ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Kitchen family remodel rough in ok cover
|
Electrical Rough-In | 9/26/2018 | 9/27/2018 | 9/27/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg 210.52(B)(2)- Small appliance branch circuits shall have no other outlets. Tapped off kitchen receptacle to feed light over sink. 300.4- Nail plates needed where bored holes do not maintain 1 1/4" from framing surface. 310.15(B)(16)- 14ga wire tapped off 20 amp branch circuit. 15 amp max on 14ga wire. 334.30- NM cable shall be supported at intervals not to exceed 4 1/2 and secure with in 12" of a box. Looks like someone other than electical contractor may have done some work.
|