Final | 10/11/2018 | 10/12/2018 | 10/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
AC connect Phone #: ###-#### Inspection requested via web by Kendra Lanham Called contractor and have verbal confirmation on ownership of work and have documentation they called permit technician and paid addition fee and has taken responsibility for all of branch circuit. Final ok
|
Final | 10/1/2018 | 10/2/2018 | 10/2/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Connected whip to A/C unit from disconnect. NOTE: owner installed disconnect and wire. Phone #: ###-#### Inspection requested via web by Kendra Lanham BCC 04-05-21- Electrical permit required to cover from outdoor panel to HVAC disconnect. Owner stated he provided conduit and wire and electrical contractor terminated wiring. Either owner pulls permit for feed to disconnect or contractor takes responcibility for entire branch circuit.
110.14- Grounding terminations in panel, up to 3 under each termination, but shall be of same size conductor. 110.26- HVAC fused disconnect shall have minimum work space provided 30" wide and 36" deep. Now located behind HVAC unit.
|