Final | 6/24/2019 | 6/25/2019 | 6/25/2019 | A | PASS |
James Ady
|
|
|
Jose Phone #: ###-#### Final ok
|
Electrical Rough-In | 5/28/2019 | 5/28/2019 | 5/28/2019 | P | CANC |
Eric Story
|
|
|
Jose- pleasw call for access Phone #: ###-#### Needed p/s
|
Permanent Service | 5/28/2019 | 5/28/2019 | 5/28/2019 | P | PASS |
Eric Story
|
|
|
Jose- pleasw call for access Phone #: ###-#### Transformer is a long distance from fire pump panel and breakers are rated at 75kva at 270/480V(will email AFCI rating as soon as given to James and Myself ) p/s u/g n ok
|
Electrical Rough-In | 4/23/2019 | 4/23/2019 | 4/23/2019 | P | PASS |
James Ady
|
|
|
Jose Phone #: ###-#### ceiling only ok to cover
|
Electrical Rough-In | 4/17/2019 | 4/17/2019 | 4/17/2019 | P | PASS |
James Ady
|
|
|
Jose Phone #: ###-####Column line 3 and 4 ceiling ok to cover
|
Electrical Rough-In | 4/11/2019 | 4/11/2019 | 4/11/2019 | P | PASS |
James Ady
|
|
|
transformer // Jose Phone #: ###-#### transformer connections only ok
|
Electrical Rough-In | 4/5/2019 | 4/8/2019 | 4/8/2019 | A | PASS |
James Ady
|
|
|
Jose Phone #: ###-#### Ceiling ok to cover to second row of columbs from South wall.
|
Electrical Rough-In | 3/18/2019 | 3/18/2019 | 3/18/2019 | P | PASS |
James Ady
|
|
|
call / Jose Phone #: ###-#### exterior walls and ceiling ok to cover Talked about Jockey pump install. Will tap off main Pump service and mount Jockey pump control over Main control. Will build strut rack to keep face of controlers even.
|
Electrical Rough-In | 1/30/2019 | 1/31/2019 | 1/31/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Pole bases only ok to cover
|
Electrical Rough-In | 11/14/2018 | 11/15/2018 | 11/15/2018 | A | PASS |
James Ady
|
|
|
Jose Phone #: ###-#### underground for site lighting ok to cover
|
Electrical Rough-In | 11/1/2018 | 11/2/2018 | 11/2/2018 | A | PASS |
James Ady
|
|
|
call when get there // UG r/i // Jose Phone #: ###-#### Underground for parking lot lighting only ok to cover
|
Conference | 10/9/2018 | 10/9/2018 | 10/9/2018 | P | PASS |
James Ady
|
|
|
Please call Jose.
Go over Fire Pump. Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed disc means on exterior of building. NFPA 20 does not allow disc between Power source and pump control panel unless supplied by multiple sources. If disc is installed, the power source becomes unreliable, and back up power is required.
|