Permit Information
Permit NumberELE18-03881
StatusFinaled
Name CAMAS ELECTRIC CONTRACTING
Site Address 4455 E WARM SPRINGS AVE
Project NameAspen Valley Senior Living
Customer Number 
ePlanReviewNo
Description
wiring for 66 unit assisted living center
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/29/20194/29/20194/29/2019PPASS
DetailsEric Story
Mark Phone #: ###-####
Card on site final ok
Final4/24/20194/25/20194/25/2019APART
DetailsJames Ady
Mark Phone #: ###-#### 110.26D Illumination in panel board rooms shall not be controled by automatic means. 210.8 Where required by 210.8 A through E, the GFCI shall be readily accessible (See definition of readily accessible. Xmas recep.) 210.8B5. Receps within 6ft of sink shall be GFCI protected.(Fitness room) Hall receps and courtyard GFCI in area C not working.
Final4/10/20194/11/20194/11/2019APART
DetailsJames Ady
Mark- final inspection for wing "A" Phone #: ###-#### Partial final "A"wing (West side of entry) OK
Electrical Rough-In4/1/20194/2/20194/2/2019APASS
DetailsJames Ady
reinspection // Mark Phone #: ###-#### Remaining areas of drop ceiling ok to cover
Electrical Rough-In3/29/20194/1/20194/1/2019APASS
DetailsJames Ady
celing- Mark Phone #: ###-#### Drop ceilings only. Salon and restrooms not ready at this time. MC ok to be supported by grid wire as per D. Degrang.
Electrical Rough-In2/26/20192/26/20192/26/2019PPASS
DetailsJames Ady
Mark Phone #: ###-#### Half wall in kitchen area only ok to cover
Electrical Rough-In2/25/20192/25/20192/25/2019PPASS
DetailsJames Ady
would like as early as possible Phone #: ###-#### Front desk half wall and soffit ok to cover
Electrical Rough-In2/21/20192/21/20192/21/2019PPASS
DetailsJames Ady
Late afternoon // Mark Phone #: ###-#### Remaining ceiling and front entry columns only ok to cover
Electrical Rough-In2/14/20192/15/20192/15/2019APASS
DetailsJames Ady
Mark Phone #: ###-#### Drop ceiling areas in cooridors ok to cover
Electrical Rough-In1/22/20191/22/20191/22/2019PPASS
DetailsJames Ady
Mark Phone #: ###-#### Remaining area ok to cover
Electrical Rough-In1/16/20191/16/20191/16/2019PPART
DetailsJames Ady
Mark-would like as late as poss if poss Phone #: ###-#### Exterior walls only. Hard lids only. No interior walls at this time Area c only
Electrical Rough-In1/11/20191/11/20191/11/2019PPASS
DetailsJames Ady
Mark Phone #: ###-#### Fornt canopy and back patio ok to cover
Electrical Rough-In12/28/201812/28/201812/28/2018PPASS
DetailsJames Ady
Mark Phone #: ###-#### area c only ok to cover
Electrical Rough-In12/3/201812/3/201812/3/2018PPASS
DetailsJames Ady
Area D r/i - Mark Phone #: ###-#### area D only ok to cover
Rough-In Permanent Service11/9/201811/13/201811/13/2018APASS
DetailsJames Ady
Mark Phone #: ###-#### Hard lids in Bathrooms only p/s u/g n ok
Electrical Rough-In10/26/201810/29/201810/29/2018APASS
DetailsJames Ady
Mark Phone #: ###-#### Do not cover ceilings in Bathrooms. Walls only. Rooms ok to cover walls and ceilings. Area "A" only
Electrical Rough-In10/12/201810/15/201810/15/2018APASS
DetailsJames Ady
Underground - Mark Phone #: ###-#### Underground for 3 parking lot lights along front of lot ok to cover