Final | 3/11/2019 | 3/11/2019 | 3/11/2019 | P | PASS |
Rock A. Hudson
|
|
|
Etta Phone #: ###-#### Final ok
|
Final | 3/7/2019 | 3/8/2019 | 3/8/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Etta Phone #: ###-#### 110.3- Open ground and up receptacle not working. Mechanical room and pantry show open grounds. 250.140- Range and dryers shall be 4 wire receptacles. 210.70- Exterior lights shall operate at all exterior entrances. finish patio ceiling. 314.16- Disposal box shall have 16 cubic inch minimum for conductors installed. 314.29- Boxes shall be fully accessible under cooktop. 334.12- NM cable shall be protected from damage under sink and shall not be installed in damp locations. Patio. 348.30- Strap furnace flex with in 12" of a box and rest not to exceed 3'. 406.6- Receptacles and switches shall have proper covers. few missing. 406.9- Receptacles installed outdoors shall be weather resistant type. Near AC. 422.31- Appliances shalll have a disconnecting means. 110.25 lockouts acceptable. Oven, dishwasher, range hood. 440.11- Furnace shall have a manual disconnecting means.
|
Permanent Service | 11/27/2018 | 11/28/2018 | 11/28/2018 | A | PASS |
Rock A. Hudson
|
|
|
Etta Phone #: ###-#### p/s o/h n ok
|
Electrical Rough-In | 10/31/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
Rock A. Hudson
|
|
|
Etta Phone #: ###-#### Corrections done. Rough in ok cover
|
Electrical Rough-In | 10/29/2018 | 10/29/2018 | 10/29/2018 | P | FAIL |
Daryl DeGrange
|
|
|
call 20 mins head- Etta Phone #: ###-#### Complete all make-ups NEC 334.30 Sscure NM within 12in. of entry of outlet boxes. KO Plug Nail plates where needed. Grounding of metal boxes
|
Conference | 10/10/2018 | 10/11/2018 | 10/11/2018 | A | PASS |
Rock A. Hudson
|
|
|
after 9am- Etta Phone #: ###-#### Owners father doing work, Discussed receptacle layouts includes upstair rail and fixed panel of sliding doors, each bathroom on dedicated 20 amp circuits, grounding electrode bent over to interior of crawl space, max height of breaker handles, secure support of NM cable, pamphlet given
|