Final | 10/11/2018 | 10/12/2018 | 10/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
|
Final | 10/10/2018 | 10/11/2018 | 10/11/2018 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman 210.8- GFCI protection on all 120 volt receptacles with in 6' of a sink and outdoors. Southeast entry has outdoor receptacle near it and end of bar has receptacle with in 6' of a sink. 314.20- All boxes installed in a combustible wall material shall be flush with combustible surface, D-5 circuit near dining room and D-11 circuit near panel wall. Contractor to correct prior to customer access. Signed TCO partial final ok
|