Final | 12/20/2018 | 12/20/2018 | 12/20/2018 | P | PASS |
Rock A. Hudson
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Rough-In Permanent Service | 10/29/2018 | 10/29/2018 | 10/29/2018 | P | PASS |
James Ady
|
|
|
I fixed it.. Inspection requested via web by Bob Glenn Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 10/25/2018 | 10/26/2018 | 10/26/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.7- Installations shall be complete. Empty light box in garage ceiling. 340.10(4)- UF shall comply with 334. 334.30 UF shall be secured with in 12" of entering PVC to island. 352.28- Cut ends of PVC shall have rough edges removed. 352.46- Where UF enter or emerges from PVC they shall be protected from damage by bushings.
|