Final | 12/28/2018 | 12/28/2018 | 12/28/2018 | P | PASS |
James Ady
|
|
|
Garage code 1957E Phone #: ###-#### Inspection requested via web by Alan Lusk corrections made final ok
|
Final | 12/26/2018 | 12/26/2018 | 12/26/2018 | P | FAIL |
Rock A. Hudson
|
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk 110.3- AC whip not complete. 210.52(A)(2)- Areas to right and left of fireplace need receptacle outlets installed with in 6' of fireplace. 406.6- Outdoor receptacle near AC cover not complete. Interior cover missing.
|
Rough-In Permanent Service | 10/23/2018 | 10/23/2018 | 10/23/2018 | P | PASS |
James Ady
|
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|