Final | 6/12/2019 | 6/13/2019 | 6/13/2019 | A | PASS |
Tom Saunders
|
|
|
Labeling of roof top units done ready for final. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin... disconnect labelling and panel labelling ok to final
|
Final | 6/6/2019 | 6/7/2019 | 6/7/2019 | P | PART |
Tom Saunders
|
|
|
Roof top units ready for final. Bruce is our contact at ###-####. We will try to call the inspector to schedule access and timing. Thank You! Phone #: ###-#### Inspection requested via web by Kelly Felin... multiple buildings...contractor having issues getting access to all spaces in buildings
verified disconnects, fuses, and service outlets on rooftops
labelling of disconnects and panels will be done as access is granted...images will be supplied
future final will need scheduled to go over HVAC unit labelling and panel labelling
|
Final | 5/21/2019 | 5/22/2019 | 5/22/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Roof Top units ready for final. Jason is our contact at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Kelly Felin 408.4- Circuit directory shall be accurately labeled as to which unit supplied with unit marked with identification of circuit or individual unit. 440.4- Overcurrent protection shall not exceed value given on name plate.
|