Final | 5/30/2019 | 5/31/2019 | 5/31/2019 | A | PASS |
Eric Story
|
|
|
access: 1234 Phone #: ###-#### Inspection requested via web by David Nelson As per 210.52 receptacle placed was corrected for wall spacing Final ok
|
Final | 5/22/2019 | 5/23/2019 | 5/23/2019 | A | FAIL |
Rock A. Hudson
|
|
|
access 1234 Phone #: ###-#### Inspection requested via web by David Nelson Correction not complete. As per Bob Archibald conditioned space connected to house with conditioned air is concidered livable space and shall comply with NEC 210.52(A). Have a call into Adele Schaffeld-Griffin to clearify, unable to reach due to in class today.
|
Final | 4/10/2019 | 4/11/2019 | 4/11/2019 | A | FAIL |
Eric Story
|
|
|
access 1234, driveway will be cleared for access Phone #: ###-#### Inspection requested via web by David Nelson As per 210.52 living spaces shall comply with wall spacing (room marked as storage has a condition heating and cooling sytem intall and as defined by IBC is livable as needs to be undre review
|
Final | 4/9/2019 | 4/10/2019 | 4/10/2019 | A | CANC |
Eric Story
|
|
|
access 1234 Phone #: ###-#### Inspection requested via web by David Nelson Provide access for dwelling unit, driveway is covered in mud and not accessible
|
Rough-In Permanent Service | 12/4/2018 | 12/5/2018 | 12/5/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson rough-in ok to cover p/s u/g n ok
|