Final | 1/9/2019 | 1/9/2019 | 1/9/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson...ok to final
|
Rough-In Permanent Service | 10/25/2018 | 10/25/2018 | 10/25/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 10/24/2018 | 10/24/2018 | 10/24/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 110.12(A)- Unused openings shall be closed by approved means. 2" KO in bottom of meterbase. 300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface. Garage. 314.25- Recessed can junction box cover shall be installed so it totally cover opening in box. near bottom of stair back cover partailly off. 352.46- Where UF cable enters or emerges from PVC conduit it shall be protected from damage by bushings. 408.7- Unused breaker openings shall be closed by aproved means.
|