Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE18-04098
StatusFinaled
Name TDR ELECTRIC
Site Address 4210 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/9/20191/9/20191/9/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Therrin Robertson...ok to final
Rough-In Permanent Service10/25/201810/25/201810/25/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Therrin Robertson
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service10/24/201810/24/201810/24/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Therrin Robertson
110.12(A)- Unused openings shall be closed by approved means. 2" KO in bottom of meterbase.
300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface. Garage.
314.25- Recessed can junction box cover shall be installed so it totally cover opening in box. near bottom of stair back cover partailly off.
352.46- Where UF cable enters or emerges from PVC conduit it shall be protected from damage by bushings.
408.7- Unused breaker openings shall be closed by aproved means.