Final | 3/12/2019 | 3/13/2019 | 3/13/2019 | A | PASS |
James Ady
|
|
|
Garage code is 7352 enter Phone #: ###-#### Inspection requested via web by Zane Robertson corrections made final ok
|
Final | 3/11/2019 | 3/12/2019 | 3/12/2019 | A | FAIL |
James Ady
|
|
|
Garage code is 7352 enter Phone #: ###-#### Inspection requested via web by Zane Robertson 314.25 Devices shall have covers(Opener receps) 422.31Appliances shall have Disc.(Both ovens, Dish/disp) 110.22 Disconect shall be identified(Furnace Disc) Install gfci recep in landscape bell box. Wire A/C.
|
Final | 3/6/2019 | 3/7/2019 | 3/7/2019 | A | CANC |
Rock A. Hudson
|
|
|
Garage code is 7352 Phone #: ###-#### >> Inspection requested via web by Zane Robertson Inspection cancelled from web by: Zane Robertson
|
Rough-In Permanent Service | 12/13/2018 | 12/14/2018 | 12/14/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage by nail plates. Above master bath switches. 300.5(H)- Where cable emerges from grade from a underground conduit they shall be prtected from damage by bushings. UF in family and kitchen. 314.25- All boxes shall have covers. Above master utility in shall part of attic. * Unable to locate AC branch circuit located at back of garage.
|
Electrical Rough-In | 11/1/2018 | 11/2/2018 | 11/2/2018 | P | PASS |
James Ady
|
|
|
Under ground for floor plug and island Phone #: ###-#### Inspection requested via web by Zane Robertson Underground only ok to cover
|