Final | 1/23/2019 | 1/24/2019 | 1/24/2019 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Final ok
|
Final | 1/22/2019 | 1/23/2019 | 1/23/2019 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 210.52 All basins shall have a receptacle located within 36" 210.52 Wall spacing shall be 6' from a cabinet in kitchen, counter receptacles do not count for wall spacing 406 tamper resistant in pantry
|
Electrical Rough-In | 11/3/2018 | 11/5/2018 | 11/5/2018 | A | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Corrections fixed Rough-in ok to cover
|
Permanent Service | 11/5/2018 | 11/5/2018 | 11/5/2018 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley
p/s u/g n ok
|
Electrical Rough-In | 11/2/2018 | 11/2/2018 | 11/2/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3(A)- Boxes installed shall be listed. Allied pancake boxes provide listing or replace. 110.3(B)- Acorn clamp shall be installed as per manufacturers instructions. Grounding electrode conductor shall be installed opposite of set screw. 300.4- Several nail plates needed through out. Garage out lights, master bed corner, master hall, fire place left side, entry, pantry switch, utility. 334.12- NM cable shall not be installed where subject to physical damage. Utility switch leg out of wall below ceiling and pulled tight. 408.3(A)(2)- Barriers shall be in place where service conductors terminate in panel.
|