Permit Information
Permit NumberELE18-04218
StatusFinaled
Name FALCON ELECTRIC INC
Site Address 2103 S PEBBLECREEK LN
Project Name 
Customer Number13745
ePlanReviewNo
Description
Complete Installation (includes room count and per: New Electrical
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/15/201910/16/201910/16/2019APASS
DetailsJames Ady
All corrections have been made. Phone #: ###-#### Inspection requested via web by Rhonda Yoast Corrections made final ok
Final10/14/201910/15/201910/15/2019PFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Rhonda Yoast 314.20Sparkrings needed on W/P receps. 440.6. Max overcurrent on A/C Nameplate is 40A 50A installed. 110.3 3way in middle bedroom is miswired
Conference10/2/201910/3/201910/3/2019ADONE
DetailsJames Ady
Please call Bill for a conference call Phone #: ###-#### Inspection requested via web by Rhonda Yoast Talked about when to schedule final. Need porwer restored after other contractor finishes up sizing service.
Conference9/4/20199/5/20199/5/2019ACANC
DetailsJames Ady
Please call Bill he will explain what is going on. Phone #: ###-#### Inspection requested via web by Rhonda Yoast
Electrical Rough-In9/5/20199/5/20199/5/2019APASS
DetailsJames Ady
Please call Bill he will explain what is going on. Phone #: ###-#### Inspection requested via web by Rhonda Yoast Rough in Patio FP ok to cover
Rough-In Permanent Service1/7/20191/8/20191/8/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Rhonda Yoast
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service1/7/20191/7/20191/7/2019PFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Rhonda Yoast...
1..NM cable less than 1 1/4" from face of wall stud shall be protected by nailplates
marked on stud
2..front den cans need made up/ complete installation
3..outlets/switches in attic by crawl spaces need installed at time of rough in for verification