Permanent Service | 11/6/2018 | 11/7/2018 | 11/7/2018 | P | PASS |
Tom Saunders
|
|
|
Re- inspection Lock Box code 155 or 1551.Verified water pipe bonding from sub-panel in garage. Phone #: ###-#### Inspection requested via web by Jack Bernard... corrections made p/s u/g reconnect ok
|
Permanent Service | 11/1/2018 | 11/2/2018 | 11/2/2018 | P | FAIL |
Tom Saunders
|
|
|
Lock box code 155 or1551 any question contact Jack ###-#### Phone #: ###-#### Inspection requested via web by Jack Bernard... 1..as per 2008 code...grounding needs brought up code...2nd ground rod shall be added 6ft apart 2..water bond needs verification..main line needs bonded within 5ft of entrance 3..per Boise City ordinance access where belongings of owner are at or in location inspector must be accompanied by someone owner or contractor
|