Final | 12/13/2018 | 12/14/2018 | 12/14/2018 | A | PASS |
Daryl DeGrange
|
|
|
Inspect mini-split unit for proper over-current protection. Phone #: ###-#### Inspection requested via web by Jonathan Poot correction complete, final ok
|
Final | 12/12/2018 | 12/13/2018 | 12/13/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot NEC 440.6 Maximum overcurrent protection from unit name plate shall be 15 ampere, 20 ampere breaker has been installed.
|
Electrical Rough-In | 11/7/2018 | 11/8/2018 | 11/8/2018 | A | PASS |
Tom Saunders
|
|
|
The addition is on the back of the home around the right side through the opened fencing. Phone #: ###-#### Inspection requested via web by Jonathan Poot... ok to cover
|