Final | 12/19/2018 | 12/20/2018 | 12/20/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot... AFC label will be installed-fused disconnect...corrections made...no card on site...ok to final
|
Final | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.24- Available fault current shall be posted with value and date calculated. 210.63- A service receptacle outlet shall be installed with in 25' of outdoor AC unit and on mezz with in 25' of air handler. 314.25- Open j-box north wall warehouse for exhaust fan. 330.30- MC located on mezz shall be secured to wall. 406.6- GFCI receptacle located in warehouse bathroom shall have a cover. IBC- Power for emergency light shall not be controlled by a wall switch.
|
Permanent Service | 11/15/2018 | 11/19/2018 | 11/19/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Rough in done under permit ELE18-03487. Fuses rated 200k AIC. Available fault current shall be posted prior to final. p/s u/g n ok
|