Permit Information
Permit NumberELE18-04454
StatusFinaled
Name SAME DAY ELECTRIC
Site Address 1704 N 12TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Added 240v circuit for hot tub
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/8/20191/9/20191/9/2019APASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Same Electric Ok final. Overhead to underground for hot tub. Hot tub GFI functions properly.
Permanent Service12/20/201812/21/201812/21/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Same Electric Service was reconnected after hours. changed from overhead to underground. Grounding is complete. p/s u/g n ok
Electrical Rough-In12/19/201812/20/201812/20/2018APASS
DetailsMark Moncarr
Needs OK to cover Phone #: ###-#### Inspection requested via web by Same Electric Ok cover trench for new underground feed. Depth meets code requirements.
Final12/6/201812/7/201812/7/2018AFAIL
DetailsMark Moncarr
###-####-Please call when on the way Phone #: ###-#### Inspection requested via web by Same Electric Table 680.9(A) requires an overhead service line not enclosed in conduit, to be a minimum of 10' horizontally outside the inside walls of a hottub or pool. If not, a height of 22.5' or more must be maintained from the top of the water line. In order for a final inspection, hottub location would need to changed, and a load calculation will need to be done as it is fed from a 90a main brkr.