Addition: Install wiring for a shipping container to be used as office space.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/27/201811/28/201811/28/2018AFAIL
DetailsRock A. Hudson
There is a padlock on the office container (the one next to the electrical panel) and the key is on the Cableone box to the right of the meter. Phone #: ###-#### Inspection requested via web by Jonathan Poot
225.39- Outdoor branch circuit disconnecting means shall be a minimum ov 60 amp for a detached structure with 3 or more circuits,
230.24(A)- Vertical clearance over flat roof top surfaces shall be a minimum of 8'.
830.44(A)(4)- Vertical clearance for commmunication cables over flat roof top surfaces shall be a minimum of 8'.
BCC- A conditional use permit is required for use of storage container in this manner.