Permit Information
Permit NumberELE18-04784
StatusFinaled
Name PRIORITY ELECTRIC
Site Address 355 W JULIA DAVIS DR
Project Name 
Customer NumberBLD18-01253
ePlanReviewNo
Description
New: Power and lighting to new anteater building.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/13/20196/13/20196/13/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins Final ok
Electrical Rough-In5/16/20195/16/20195/16/2019PPASS
DetailsRock A. Hudson
Corbin Phone #: ###-#### Inspection requested via web by Tom Jenkins
Mechanical closet walls rough in ok cover
Electrical Rough-In4/16/20194/17/20194/17/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Ceiling for foam rough in ok cover
Rough-In Permanent Service3/28/20193/28/20193/28/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tom Jenkins
Service only at this time. 65k rated main @ 240 volt. p/s u/g n ok
Electrical Rough-In3/6/20193/6/20193/6/2019PPASS
DetailsRock A. Hudson
Block inspection Phone #: ###-#### Inspection requested via web by Tom Jenkins
Block boxes rough in ok cover
Electrical Rough-In1/29/20191/29/20191/29/2019PPASS
DetailsRock A. Hudson
Uffer inspection. Please inspect before 2pm if possible. Phone #: ###-#### Inspection requested via web by Tom Jenkins
Concrete encased electrode rough in ok cover
Electrical Rough-In1/25/20191/28/20191/28/2019AFAIL
DetailsRock A. Hudson
Pad conduits Phone #: ###-#### Inspection requested via web by Tom Jenkins
314.29 Boxes, Conduit Bodies, and Handhole Enclosures to Be Accessible. Boxes, conduit bodies, and handhole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or structure or, in underground circuits, without excavating sidewalks, paving, earth, or other substance that is to be used to establish the finished grade.
Ant eater pond actuators located too deep in ground box to be accessible.
Electrical Rough-In1/24/20191/24/20191/24/2019PPASS
DetailsRock A. Hudson
Inspect underground conduit Phone #: ###-#### Inspection requested via web by Tom Jenkins
Underground along north fence, allow for repair of damaged 3/4" pvc. rough in ok cover
Electrical Rough-In1/21/20191/22/20191/22/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Tom Jenkins remaining underground between buildings ok to cover
Electrical Rough-In1/17/20191/17/20191/17/2019PPART
DetailsRock A. Hudson
Underground cover Phone #: ###-#### Inspection requested via web by Tom Jenkins
Utility underground conduits from transformer about 1/2 way to service location rough in ok cover.