Final | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | PASS |
James Ady
|
|
|
GARAGE CODE 4224 OR 10020
THANK YOU Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made final ok
|
Final | 4/5/2019 | 4/8/2019 | 4/8/2019 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn 300.15- At each outlet point NM cable shall terminate in a box. Above fireplace 14-2 left in wall shall terminate in a box. 314,17(B)- Where NM cable enters a box the jacket shall enter box 1/4" [ast clamp minimum in level 1 bathroom receptacle. 422.31- Hard wired range hood shall have a disconnecting means. Lock out is acceptable as per 110.25.
|
Rough-In Permanent Service | 1/8/2019 | 1/9/2019 | 1/9/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|