Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00108
StatusFinaled
Name LEA ELECTRIC LLC
Site Address 3075 W CRESCENT RIM DR
Project Name 
Customer Number3902
ePlanReviewNo
Description
New: Full electrical installation in ground-up construction including underground, conduit, wiring, gear, panels, receptacles, lighting, lighting control, telecomm and fire alarm
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/6/20202/6/20202/6/2020PPASS
DetailsEric Story
Inspection outside building for final Phone #: ###-#### Inspection requested via web by Tom Betty
Occ card signed-Final ok
Final1/30/20201/31/20201/31/2020APART
DetailsEric Story
Rooms storage 111 , corridor 110A , trash 112 , bicycle 113 , storage 114 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Areas as noted ok
Final1/29/20201/29/20201/29/2020PPART
DetailsEric Story
Units 301 , 101 , 102 , 107 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Temp occ signed for finacing only no moving in at this point
Final1/28/20201/28/20201/28/2020PPART
DetailsEric Story
Finals for units 307 , 306 , 201 , 206 , 207 , 208 Phone #: ###-#### Inspection requested via web by Tom Betty
Units as requested ok
Final1/22/20201/23/20201/23/2020APART
DetailsEric Story
unit 106 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 106 ok to continue
Final1/15/20201/15/20201/15/2020PPART
DetailsRock A. Hudson
Re- inspect units for finals ,breaker lock outs, wine room unit 205 and GFCI fix egress lights.Final parking garage .Grid ceiling 110A 1st corridor roughin and grid ceiling in parking Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 103, 104, 105, 203, 204, 205 TCO ok, 302 lock outs in.
Level 1 East egress light ok.
Parking garage TCO ok
Some items yet to complete for actual TCO.
Site pole bases with exposed wiring. Not ready. Exterior not checked for final.
Mechanical room- support sub-feed MCs, remove expose THHN above panels.
Remove extension cord thru wall from temp office area in parking garage.
Electrical Rough-In1/15/20201/15/20201/15/2020PPASS
DetailsRock A. Hudson
Re- inspect units for finals ,breaker lock outs, wine room unit 205 and GFCI fix egress lights.Final parking garage .Grid ceiling 110A 1st corrridor roughin and grid ceiling in parking Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Basement elevator grid rough in ok cover.
Level 1- 110(A) corridor grid rough in ok cover.
Final1/14/20201/14/20201/14/2020PNR
DetailsRock A. Hudson
Rough in Grid ceiling 2nd and corridor 109 1st . Finals 3rd, 2nd ,1st 109 floor corridors, Stairs 1, 2 , 3 and units 103 , 104 , 105 , 203 , 204 , 205 Phone #: ###-#### Inspection requested via web by Tom Betty
Disconnecting means shall be provided for all hardwired appliances, hoods, furnaces, water heaters, microwaves, ovens. all units. 422.31.
105 bathroom GFCIs in-op. 205 no access to wine room, condencing unit for wine room not complete. out egress not complete east entance.
Electrical Rough-In1/14/20201/14/20201/14/2020PPASS
DetailsRock A. Hudson
Rough in Grid ceiling 2nd and corridor 109 1st . Finals 3rd, 2nd ,1st 109 floor corridors, Stairs 1, 2 , 3 and units 103 , 104 , 105 , 203 , 204 , 205 Phone #: ###-#### Inspection requested via web by Tom Betty
Units noted TCO ok. Grid noted rough in ok cover
Electrical Rough-In1/10/20201/10/20201/10/2020APASS
DetailsDaryl DeGrange
3rd floor corridor drop ceiling and unit 302 final Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty r/i ok cover 3rd floor corridor ceiling, unit 302 Final ok
Electrical Rough-In12/31/20191/2/20201/2/2020APASS
DetailsEric Story
Bath floor heat unit 101 Call John Phone #: ###-#### Inspection requested via web by Tom Betty
Both baths in unit 101
Electrical Rough-In12/23/201912/23/201912/23/2019APASS
DetailsEric Story
Floor heat unit 107 and outside trench Phone #: ###-#### Inspection requested via web by Tom Betty
Floor heat unit 107@front U/G along ramp ok to cover
Electrical Rough-In12/12/201912/12/201912/12/2019APASS
DetailsEric Story
Bath room floor heat unit 207 Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 207 floor heat ok to cover
Electrical Rough-In12/4/201912/4/201912/4/2019APASS
DetailsEric Story
First floor hallway building B drop ceiling Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Ceiling in 1st floor and unit 206 floor heat ok ot cover
Electrical Rough-In11/27/201911/27/201911/27/2019APASS
DetailsEric Story
Floor heat units 301 and 201 call craig Phone #: ###-#### Inspection requested via web by Tom Betty
Floor heat in units 201@301 ok to cover
Final11/21/201911/21/201911/21/2019ACANC
DetailsEric Story
Final on unit 106 Phone #: ###-#### Inspection requested via web by Tom Betty
No final given at this time
Electrical Rough-In11/21/201911/21/201911/21/2019PPASS
DetailsEric Story
Final on unit 106 Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 106 ok to stage furniture
North corridor of 1st floor ok to cover
Electrical Rough-In11/20/201911/20/201911/20/2019APASS
DetailsEric Story
Bath floor heating unit 304 Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 304 floor heat ok to cover
Electrical Rough-In11/15/201911/15/201911/15/2019PPASS
DetailsJames Ady
Unit 303 Floor Heat
Contact Craig Timmons
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Floor heat only ok to cover
Electrical Rough-In11/13/201911/13/201911/13/2019APASS
DetailsMark Moncarr
Second floor hall drop ceiling Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Ok cover soffits 2nd floor. Get your tools on Betty!
Electrical Rough-In11/6/201911/6/201911/6/2019APASS
DetailsEric Story
Third floor hallway drop ceiling Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
3rd floor soffit hard lids only (suspended ceiling will be inspected on other dates)
Electrical Rough-In10/25/201910/25/201910/25/2019APASS
DetailsEric Story
Soffit unit 101 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 101 soffits ok to cover
Electrical Rough-In10/18/201910/18/201910/18/2019APASS
DetailsEric Story
Floor heat unit 104 and drop soffit unit 102 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Floor heat for unit 104 and drop ceiling in 102 ok to cover
Electrical Rough-In10/16/201910/16/201910/16/2019APASS
DetailsEric Story
Floor heating units 105 and 205. Soffit unit 107 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units as requested ok to cover soffit and floor heat
Electrical Rough-In10/9/201910/10/201910/10/2019APASS
DetailsEric Story
soffit inspection room 207 "0" Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 207 soffit ok to cover
Electrical Rough-In10/3/201910/4/201910/4/2019APASS
DetailsEric Story
Floor heating unit 203 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 204 not 203 as requested ok to cover floor heat
Electrical Rough-In10/1/201910/1/201910/1/2019APASS
DetailsEric Story
Soffit unit 201 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 201 soffits ok to cover
Electrical Rough-In9/24/20199/24/20199/24/2019APASS
DetailsEric Story
Soffits unit 202 , 206 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 202,206,208 drop ceilngs ok to cover
Electrical Rough-In9/12/20199/12/20199/12/2019APASS
DetailsEric Story
Soffits units 303 and 304 Phone #: ###-#### Inspection requested via web by Tom Betty
Units 303@304 siffits ok to cover
Electrical Rough-In9/9/20199/9/20199/9/2019APASS
DetailsEric Story
Soffit unit 301 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Soffits as requested ok to cover
Electrical Rough-In9/6/20199/6/20199/6/2019APASS
DetailsEric Story
Unit 302 bath room floor heating call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Floor heat in unit 302 ok to cover
Electrical Rough-In8/26/20198/26/20198/26/2019APASS
DetailsEric Story
Drop ceilings units 103 and 106 Phone #: ###-#### Inspection requested via web by Tom Betty
Units as requested drop ceilngs ok to cover
Electrical Rough-In8/20/20198/20/20198/20/2019APASS
DetailsEric Story
Soffit units 104 and 105 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Soffits as requested ok to cover
Electrical Rough-In8/6/20198/7/20198/7/2019APASS
DetailsEric Story
rough in sofit room 203 and 204 ron Phone #: ###-#### Inspection requested via web by Tom Betty
Rooms 203@204 hard lid ceilings ok to cover
Electrical Rough-In7/31/20198/1/20198/1/2019APASS
DetailsEric Story
Unit 102 Call Ron Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 102 ok to cover
Electrical Rough-In7/29/20197/29/20197/29/2019APASS
DetailsEric Story
Units 101 , 107 , trash rm. , bike rm. , storage , hall and drop ceiling 205 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units as requested ok to cover
Electrical Rough-In7/17/20197/18/20197/18/2019APASS
DetailsEric Story
Unit 207 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 207 ok to cover
Electrical Rough-In7/11/20197/12/20197/12/2019APASS
DetailsEric Story
Units 201 , 202 , 208 , Comm rm 2nd floor and stairs #1 Phone #: ###-#### Inspection requested via web by Tom Betty
Areas as requested ok to cover
Electrical Rough-In6/27/20196/27/20196/27/2019APASS
DetailsEric Story
Unit 206 , corridor and stairs #2 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Unit 206 and 2nd floor corridor+stair 3 ok to cover
Electrical Rough-In6/21/20196/21/20196/21/2019APASS
DetailsRock A. Hudson
Units 301 , 303 , 304 , trash rm and storage Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
All panels missing bushings on feeders.
Areas noted and adding stair 1 level 1 rough in ok cover
Electrical Rough-In6/17/20196/17/20196/17/2019APASS
DetailsEric Story
Drop ceiling unit 302 , Phone #: ###-#### Inspection requested via web by Tom Betty
Drop ceilng in unit 302 ok to cover thru-out
Electrical Rough-In6/14/20196/14/20196/14/2019APASS
DetailsEric Story
3RD floor hallway , lobby and comm rm. Phone #: ###-#### Inspection requested via web by Tom Betty
3rd floor drop ceilngs in lobby and comm room ok to cover
Electrical Rough-In5/28/20195/28/20195/28/2019ACANC
DetailsEric Story
units 103 , 104 , 105 , 106 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units as requested and stair 1@2 floors 2@3 ok to cover
Electrical Rough-In5/13/20195/13/20195/13/2019PPASS
DetailsEric Story
Inspection originally scheduled on ELE19-00903. Added her per Eric Story
Electrical Rough-In4/24/20194/25/20195/13/2019PPASS
DetailsEric Story
Inspection originally scheduled on ELE19-00903. Added her per Eric Story
Temporary Service1/14/20191/15/20191/15/2019PPASS
DetailsEric Story
Contact Craig Timmons
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
t/s u/g n ok