Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-00127
StatusFinaled
Name MOUNTAIN POWER ELECT
Site Address 1008 W MILLER ST
Project Name 
Customer Number19-002
ePlanReviewNo
Description
Addition: Provide and install four pole lights and electrical service for the Temporary Parking Lot JRS Properties III LP project. Associated with permit # GRD18-00052
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/15/20195/16/20195/16/2019APASS
DetailsRock A. Hudson
The lock code is 9102. Please call Marcus Stevens with any questions ###-####. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Final ok
Permanent Service3/5/20193/5/20193/5/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jeremy Cloud p/s u/g n ok
Permanent Service2/11/20192/11/20192/11/2019PFAIL
DetailsRock A. Hudson
Inspect parking lot service to energize. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
110.24- Available fault current shall be posted prior to permanent service inspection with value and date calculated.
250.142- Grounded circuit conductor shall be allowed to ground non-current carrying metal parts of an enclosure of a service disconnecting means. Grounded conductor is bonded in CT can. Equipment ground through raceway is a parallel path to the grounded conductor. Remove equipment ground from CT can to service disconnecting means.
Electrical Rough-In1/15/20191/16/20191/16/2019PPASS
DetailsRock A. Hudson
Inspect underground conduit and light pole bases for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
As noted rough in ok cover
Electrical Rough-In1/11/20191/14/20191/14/2019APASS
DetailsRock A. Hudson
Inspect underground conduit for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Underground to pole bases rough in ok cover