Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-00155
StatusFinaled
Name A M E ELECTRIC
Site Address 1001 N AMERICANA BLVD
Project Name 
Customer Number180669
ePlanReviewNo
Description
Alteration: wire up pump house that is being rebuilt
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/10/20195/13/20195/13/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by A.M.E. Office Final ok
Permanent Service4/17/20194/18/20194/18/2019APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by A.M.E. Office p/s u/g n ok
Electrical Rough-In3/11/20193/12/20193/12/2019APASS
DetailsRock A. Hudson
call Dean with questions , this is for a lid cover inspection Phone #: ###-#### Inspection requested via web by A.M.E. Office
ceiling rough in ok cover
Electrical Rough-In2/5/20192/6/20192/6/2019APASS
DetailsRock A. Hudson
Dean Hunsperger is the contact person (electrician). He needs an underground inspection. Thank you Phone #: ###-#### Inspection requested via web by A.M.E. Office
Concrete encased electrode located on exterior of foundation stubbed out of footing on east side under 2" PVC shall be protected from weather and direct contact with earth. Electrical contractor to encase stub and connection in concrete to protect. Interior and 2" exterior underground rough in ok cover