Permit Information
Permit NumberELE19-00177
StatusFinaled
Name POWER PLUS INC
Site Address 1301 N ORCHARD ST Unit: STE 200
Project Name 
Customer Number5480
ePlanReviewNo
Description
Alteration: remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/28/20193/1/20193/1/2019PPASS
DetailsRock A. Hudson
chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
Final2/28/20192/28/20192/28/2019PFAIL
DetailsRock A. Hudson
Chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
No ceiling inspection, wireman provided a ladder for spot check. Office furniture not complete. Whips to be removed until can be terminated.
BCC 4-05-32 No code violation to be retained.
330.30- Existing MC installed feeding conference room table is exposed to physical damage and shall be removed, or replace with other approved wiring method.
Electrical Rough-In2/1/20192/1/20192/1/2019APASS
DetailsRock A. Hudson
Karl Miller is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Small walls added thru out entire floor, check print. Rough in ok cover