Final | 3/21/2019 | 3/21/2019 | 3/21/2019 | P | PASS |
Eric Story
|
|
|
Lee Phone #: ###-#### Final ok
|
Electrical Rough-In | 3/7/2019 | 3/8/2019 | 3/8/2019 | A | PASS |
Eric Story
|
|
|
Lee-(husband) Phone #: ###-#### Detached shop ok to cover(met 20amp requirement with outlet to left of service and all other 15 amp, only one garage bay)
|
Permanent Service | 3/8/2019 | 3/8/2019 | 3/8/2019 | P | PASS |
Eric Story
|
|
|
Lee-(husband) Phone #: ###-#### Owner stated IDPCO was fine with meter at the height he installed it p/s o/h n ok
|
Conference | 2/27/2019 | 2/28/2019 | 2/28/2019 | A | DONE |
Eric Story
|
|
|
please call before arriving Lee Phone #: ###-#### Discussed service requirements and IDPCO for meter. Owner will drop meter for IDPCO and install a 100 main breaker panel or meter main or find a listed tie down for SQD breaker in a GE panelboard
|
Conference | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | PASS |
Rock A. Hudson
|
|
|
call for access- Lee Phone #: ###-#### Owner to install minimum required for shop, 1 auto bay, 1 man door, 1 luminaire, discussed protections of NM cables below 8', tamper resistant receptacles, GFCI protection, pamphlet given.
|
Conference | 1/17/2019 | 1/18/2019 | 1/18/2019 | A | PASS |
James Ady
|
|
|
Call 20 minutes before to meet // Lee (husband) Phone #: ###-#### Owner was not sure on scope of project. Needed advice on getting 100A service feed to shop. Only has 100A feed to house. Informed him a service upgrade needed to be done.
|