Permit Information
Permit NumberELE19-00288
StatusFinaled
Name CUSTOM ELECTRIC
Site Address 6803 W OVERLAND RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Lighting improvements. Addition of electrical components to mezzanine and restrooms. Clean-up of existing electrical junction boxes.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/2/20195/3/20195/3/2019APASS
DetailsRock A. Hudson
Contact - Neil Adams ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder
No card posted. Final ok
Final4/30/20195/1/20195/1/2019AFAIL
DetailsRock A. Hudson
Contact is Neil Adams @ ###-#### Phone #: ###-#### Inspection requested via web by Todd Alder
110.26(A)(4)- Disconnect door shall open to a minimum of 90 degrees. Disconnect located in office. Move or remove.
210.63- A receptacle outlet shall be located with in 25' of AC unit.
314.29- Covers for conduit bodies shall be accessible with out damage to wall finish. LB located to right of main disconnect.
406.5- Receptacle outlets shall be securely mounted in place. Single receptacle mezz.
440.6- AC overcurrent protection shall not exceed value noted on nameplate. 50 amp installed 40 amp max.
BCC4 05-32- Code violation not to be retained.
Electrical Rough-In2/20/20192/21/20192/21/2019APASS
DetailsTom Saunders
Bathroom rough in needs looked at. Please call Neil (###-####) 30 minutes before inspection so I can make sure the door is unlocked. Phone #: ###-#### Inspection requested via web by Neil Adams...
ok to cover
Electrical Rough-In1/28/20191/29/20191/29/2019PPASS
DetailsEric Story
please call Neil Adams 30 minutes prior to inspection to ensure the building is unlocked. Phone #: ###-#### Inspection requested via web by Neil Adams
Mezzanine area ceiling deck ok to cover