Final | 4/1/2019 | 4/2/2019 | 4/2/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake... basement addressed...ok to final
|
Final | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | PART |
Rock A. Hudson
|
|
|
Temp final for main level only, basement needs electrical safed off. Approval of main floor to allow TI permits to proceed. Corrections to be completed 4-1-19.
|
Final | 3/28/2019 | 3/29/2019 | 3/29/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake BCC 4 05 32- Code violations not to be retained, Basement area. 314.23- All boxes shall be secured to structure. 314,25- All boxes shall have covers. 330.30- MC and flex shall be secured and supported. 358.30- EMT shall be supported and secured. 400.12- Flexible cords shall not be used for structural wiring. Basement bath fan. 406.6- All receptacles shall have covers. Main level check out OK.
|
Electrical Rough-In | 2/13/2019 | 2/13/2019 | 2/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
Wall cover. Patrick is contact please call Phone #: ###-#### Inspection requested via web by Ryan Wake Vanilla space so no show window receptacles included on print. May be required depending on occupant. Walls and ceiling rough in ok cover
|