Complete Installation (includes room count and per: electrical rough in and perm service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/6/201911/7/201911/7/2019APASS
DetailsEric Story
Home owner will be there all day Phone #: ###-#### Inspection requested via web by Charles Davis
Final ok for work performed, job finished by others on permit # ELE19-04258 as specified on permit details
Rough-In Permanent Service2/18/20192/19/20192/19/2019APASS
DetailsDaryl DeGrange
copper grounding installed and encased in 2" of concrete-have pictures of installation Phone #: ###-#### Inspection requested via web by Charles Davis rough-in p/s u/g n ok
Rough-In Permanent Service2/14/20192/15/20192/15/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Charles Davis
250.32(A)- Seperate garage shall have a grounding electrode system and conductor installed.
314.25- Recessed Can junction box covers shall be completely installed as per instructions.
2 mechanical room, 1 kitchen, 1 down front bedroom.
440.6- Furnace shall be fed by minimum circuit notedd on name plate. 20 amp needed 15 amp installed.