Final | 4/30/2019 | 5/1/2019 | 5/1/2019 | A | PASS |
Eric Story
|
|
|
garage code 6074 Phone #: ###-#### Inspection requested via web by Heath Thomas Final OK
|
Rough-In Permanent Service | 2/21/2019 | 2/22/2019 | 2/22/2019 | A | PASS |
Rock A. Hudson
|
|
|
Fireplace outlet access will be there on final, can''t make it until sheetrock is installed. Double stud above panel for wire protection. Please contact Heath @ ###-#### with questions. Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 2/20/2019 | 2/21/2019 | 2/21/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas 300.4- nail plates needed on front garage light, above panel, master bath vanity receptacle 45 degree corner. 314.25- Recessed can junction box cover shall be installed flush with box as per instructions. patio, main bath over tub. 314.29- Access shall be provided for fireplace receptacle box.
|