Final | 4/16/2019 | 4/17/2019 | 4/17/2019 | P | PASS |
Rock A. Hudson
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Icon Electric Final ok
|
Final | 4/15/2019 | 4/15/2019 | 4/15/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Icon Electric 210.12- All electrica outlets located in a bedroom area shall have AFCI protection. 408.4- Circuit directory shall accurately identify each circuits purpose. #5 breaker is master bedroom. * Re-inspection fee accessed.
|
Final | 4/4/2019 | 4/8/2019 | 4/8/2019 | A | FAIL |
Tom Saunders
|
|
|
re inspection Phone #: ###-#### Inspection requested via web by Icon Electric... corrections not made...next inspection will include reinspection fee if not corrected
|
Final | 4/1/2019 | 4/4/2019 | 4/4/2019 | A | FAIL |
Eric Story
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric 210.12 All bedrooms are required to have AFCI protection (Master bed is non compliant)
|
Electrical Rough-In | 2/26/2019 | 2/27/2019 | 2/27/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Icon Electric Rough in ok cover
|
Permanent Service | 2/27/2019 | 2/27/2019 | 2/27/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Icon Electric We will add inspection this one time. It is not our job to fix your missed requests. p/s u/g n ok
|
Rough-In Permanent Service | 2/26/2019 | 2/27/2019 | 2/26/2019 | A | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Icon Electric Inspection cancelled from web by: Icon Electric
|
Electrical Rough-In | 2/25/2019 | 2/26/2019 | 2/26/2019 | A | FAIL |
Rock A. Hudson
|
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric 210.52(A)- Required receptacle outlet located in family room under window does not have wiring installed. 250.68(A)- Connection to gounding electrode system shall be sccessible. Mudring missing. 408.3(A)(2)- Barriers shall be in place to prevent accidental contact at line side terminals of panel. * Please make sure all types of inspections needed are included in request. Permanent service appears ready but not included in request
|