Permit Information
Permit NumberELE19-00722
StatusFinaled
Name TESLA ELECTRIC LLC
Site Address 300 E PENNSYLVANIA ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: complete installation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/17/20206/17/20206/17/2020PPASS
DetailsJames Ady
Lockbox code 1987 on water spigot in front of garage. Inspection requested via web by Caleb Gaylord Corrections made final ok
Final6/15/20206/16/20206/16/2020AFAIL
DetailsRock A. Hudson
screened // Tony Phone #: ###-#### 200.9- White conductor when used for other than grounded conductors shall be re-identified other than white. 210.8(A)- All receptacle outlets installed for bathroom vanities shall have GFCI protection. Master bath. 210.52(C)- Pantry counter top areas shall have receptacle outlets installed so that no point on counter is more than 24" from a receptacle outlet. 250.94- Inter systme bond shall be installed on north side of house. 314.16- Boxes shall be of sufficient size for conductors installed. 8 cubic inch box installed for island counter receptacle with 11.25 cubic inches of conductor installed. 348.30- Metal flex for disposal shall be secured by approved means with in 12" of box. 406.12- All receptacle outlets installed in house shall be tamper resistant type. Kitchen GFCI receptacles.
April with Tesla Electric ###-#### called and stated she did not request an inspection and would check into it and find out who did.
Electrical Rough-In3/6/20193/7/20193/7/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Caleb Gaylord
Rough in ok cover.
Electrical Rough-In3/5/20193/6/20193/6/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Caleb Gaylord
210.52(A)(1)- Receptacle outlets located in pantry shall be on a small appliance branch circuit.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Several locations through out.
300.15- 14-2 located in ceiling near pantry shall terminate in a box.
* Fireplace switch box empty.