Final | 6/17/2020 | 6/17/2020 | 6/17/2020 | P | PASS |
James Ady
|
|
|
Lockbox code 1987 on water spigot in front of garage. Inspection requested via web by Caleb Gaylord Corrections made final ok
|
Final | 6/15/2020 | 6/16/2020 | 6/16/2020 | A | FAIL |
Rock A. Hudson
|
|
|
screened // Tony Phone #: ###-#### 200.9- White conductor when used for other than grounded conductors shall be re-identified other than white. 210.8(A)- All receptacle outlets installed for bathroom vanities shall have GFCI protection. Master bath. 210.52(C)- Pantry counter top areas shall have receptacle outlets installed so that no point on counter is more than 24" from a receptacle outlet. 250.94- Inter systme bond shall be installed on north side of house. 314.16- Boxes shall be of sufficient size for conductors installed. 8 cubic inch box installed for island counter receptacle with 11.25 cubic inches of conductor installed. 348.30- Metal flex for disposal shall be secured by approved means with in 12" of box. 406.12- All receptacle outlets installed in house shall be tamper resistant type. Kitchen GFCI receptacles. April with Tesla Electric ###-#### called and stated she did not request an inspection and would check into it and find out who did.
|
Electrical Rough-In | 3/6/2019 | 3/7/2019 | 3/7/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Caleb Gaylord Rough in ok cover.
|
Electrical Rough-In | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Caleb Gaylord 210.52(A)(1)- Receptacle outlets located in pantry shall be on a small appliance branch circuit. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Several locations through out. 300.15- 14-2 located in ceiling near pantry shall terminate in a box. * Fireplace switch box empty.
|