Permit Information
Permit NumberELE19-00875
StatusFinaled
Name GLENN ELECTRIC
Site Address 5711 E HOOTOWL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH & PERM SERVICE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/30/20195/30/20195/30/2019APASS
DetailsJames Ady
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made final ok
Final5/24/20195/24/20195/24/2019AFAIL
DetailsRock A. Hudson
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
314.25- Buried recessed can hall out guest bedroom.
410.16- Guest closet shall have completely enclosed lamps. Globe missing.
Rough-In Permanent Service3/19/20193/19/20193/19/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service3/18/20193/18/20193/18/2019PFAIL
DetailsRock A. Hudson
please move inspection to PM today. Phone #: ###-#### Inspection requested via web by Bob Glenn
250.64(D)(1)- Grounding electrode conductor tap shall extend to the inside of each disconnecting means enclosure. Looping through 1 disconnecting means to another creates future difficulties.
300.4- Nail plates needed in kitchen island.
334.12- NM cable shall not be installed where subject to damage. Garage truss pinch point gang nail may damage NM cable.
Rough-In Permanent Service3/15/20193/18/20193/18/2019ACANC
DetailsRock A. Hudson
Contact Troy with any question or concerns. ###-####
Thanks! Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn