Permit Information
Permit NumberELE19-00898
StatusFinaled
Name SOESBE ELECTRIC LLC
Site Address 200 N 3RD ST Unit: 110
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Adding 20 6” cans and 3 outlets
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/3/20206/4/20206/4/2020PPASS
DetailsRock A. Hudson
John Sutton will be in his office at the end of the hall all afternoon and he will let you into the front area for inspection please call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe No card posted. Final ok
Electrical Rough-In9/19/20199/20/20199/20/2019APASS
DetailsRock A. Hudson
Key for access will be right down the hall at J E Suttons office. Just need approval for ceiling grid cover. Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Corrections complete, Thank you. Grid rough in ok cover.
Electrical Rough-In3/18/20193/19/20193/19/2019APASS
DetailsRock A. Hudson
Need ok to cover new wall while we figure out what to do with grid ceiling thanks. Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Wall only rough in ok cover
Electrical Rough-In3/14/20193/15/20193/15/2019AFAIL
DetailsRock A. Hudson
Key for unit in northwest corner is in J E Suttons office. Need ok to Sheetrock new wall and put grid back in rooms with new cans call with any questions thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Unit accually 100.
110.3- Recessed can covers shall be installed as per manufacturers instructions.
314.17(A)- Unused openings shall be closed by approved means.
BCC 4 05 32- no code violation to be retained. As noted on building permit, support or remove all electrical.
300.11- Raceways and cables shall not be supported by grid.
314.23- Electrical boxes shall be secured to structure.
314.25- All boxes shall have covers installed.
348.30- FMC shall be supported at intervals ot to exceed 4 1/2' and be secured with in 12" of a box.
358.30- EMT shall shall be supported at intervals not to exceed 10' and secured with in 3' of a box.