Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberELE19-00905
StatusFinaled
Name HUFFAKER GLEN D
Site Address 11068 W MUSKET ST
Project NameHuffaker remodel
Customer Number 
ePlanReviewNo
Description
move lights, add fan, remove outlet
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/7/20205/8/20205/8/2020APASS
DetailsTom Saunders
*screened* Interior, virtual inspection requested - Nicole Phone #: ###-####... ok to final..inspection done by images as per COVID19 requirements
ELE-Request for Extension12/16/201912/16/201912/16/2019APASS
DetailsDaryl DeGrange
Request for permit extension approved for additional 180 days
Electrical Rough-In6/11/20196/12/20196/12/2019APASS
DetailsTom Saunders
Nicole (wife) Phone #: ###-####....
rough ok to cover...corrections made
Electrical Rough-In5/13/20195/16/20195/16/2019AFAIL
DetailsMark Moncarr
Nicole Phone #: ###-####
1. Ground screw needed for metal box.
2 Seperate #12 from #14 wires.
3. I didnt see box buried in wall on first inspection. Homeowner informed me there was a remodel prior to them buying home. There was another wire tucked between some studs. May be hot.
3. Box to be cut in in kitchen cabinet on opposite wall and install a blank plate.
Electrical Rough-In5/9/20195/10/20195/10/2019AFAIL
DetailsMark Moncarr
Nicole (homeowner)-please go out after 9:30 am-frame insp is PM Phone #: ###-####
1. 1/2" connectors needed in can light and fan.
2. Changed out metal junction box to a larger cubic inch box to allow for box fill.
3. All wires need to be stapled within 8" of box it enters.
Final3/14/20193/18/20193/18/2019ACANC
DetailsTom Saunders
Nicole Phone #: ###-####...homeowner need conference instead
Conference3/18/20193/18/20193/18/2019APASS
DetailsTom Saunders
Nicole Phone #: ###-####...
discussed the wiring to add toilet and shower in downstairs utillity rm...access to junction boxes, required damp location light, and placement of exhaust fan. GFI protection outlet within 6ft of sink