Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00906
StatusFinaled
Name PULSE ELECTRIC & CONTROLS
Site Address 480 N LATAH ST
Project Name 
Customer Number251
ePlanReviewNo
Description
Addition: New 400 amp panel to supply existing and new addition. Power and lighting per plan.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/19/20197/19/20197/19/2019APASS
DetailsEric Story
Will be on-site making equipment connections by 8 am. Should completed by 10 Phone #: ###-#### Inspection requested via web by Sean Patton
New permit required for install of equipment.
Occ card signed
Final ok
Final7/17/20197/18/20197/18/2019ANR
DetailsRock A. Hudson
I will be onsite by 8 am. Phone #: ###-#### Inspection requested via web by Sean Patton
FRP repair, Covers off boxes. will recall.
Electrical Rough-In6/25/20196/26/20196/26/2019APASS
DetailsEric Story
Approval for cover in rooms with grid. I will be onsite at 9:30 Phone #: ###-#### Inspection requested via web by Sean Patton
Areas with suspended ceiling are ok to cover
Rough-In Permanent Service6/14/20196/14/20196/14/2019PPASS
DetailsRock A. Hudson
I will be on-site after 11 and throughout the day Phone #: ###-#### Inspection requested via web by Sean Patton
Service only. Grounding electrode conductor to underground metal water pipe shall be sized to the total of parallel conductors as per 250.66. Will check in future due to supplemental electrodes installed. Availiable fault current will be verified in future due to Idaho Power has not provided transformer or service entrance conductors yet. Fused disconnecting means installed.
p/s u/g n ok
Electrical Rough-In6/3/20196/3/20196/3/2019PPASS
DetailsEric Story
Wall inspection for cover. Late afternoon is best. I will not be back to site until 1pm.
Phone #: ###-#### Inspection requested via web by Sean Patton
Walls only ok to cover
Rough-In Permanent Service3/27/20193/28/20193/28/2019APASS
DetailsMark Moncarr
Underground inspection for cover. Section of underground work is near the alley South end of building. I will not be onsite. GC has office in downstairs basement. His number is ###-#### Phone #: ###-#### Inspection requested via web by Sean Patton Ok cover 4-2" conduits. 4th conduit was added for LV.