Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-00934
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 101 S CAPITOL BLVD
Project Name 
Customer Number78261
ePlanReviewNo
Description
Alteration: Suite 1750:
1) Demo switches, data drops and receptacles as required.
2) Remove (8ea) existing 2x4 light fixtures.
3) Provide and install (9ea) new duplex receptacles.
4) Provide and install (3ea) GFCI receptacle.
5) Provide and install (1ea) Arli
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/14/20195/15/20195/15/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Steven Ragan Final ok
Final5/10/20195/14/20195/14/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Steven Ragan
210.8(B)- All 15 and 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. Refer, disposal.
Final5/10/20195/13/20195/10/2019ACANC
DetailsRock A. Hudson
Phone #: ###-#### >> Inspection requested via web by Steven Ragan Inspection cancelled from web by: Steven Ragan
Final5/9/20195/10/20195/10/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Steven Ragan
Wet floor glue through out. Recall.
Electrical Rough-In4/23/20194/24/20194/24/2019APASS
DetailsRock A. Hudson
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover
Electrical Rough-In4/19/20194/22/20194/22/2019AFAIL
DetailsRock A. Hudson
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan
300.11- Cables and raceways shall not be supported by the ceiling assembly including ceiling suport wires. Cables moved from short support wires to ceiling support wires.
Electrical Rough-In4/18/20194/19/20194/19/2019AFAIL
DetailsRock A. Hudson
Ceiling rough-in Phone #: ###-#### Inspection requested via web by Steven Ragan
300.11- Support wires used to support cables and raceways shall be secured at both ends.
314.25- Boxes covers shall be installed. break room top of wall.
Electrical Rough-In3/20/20193/20/20193/20/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Steven Ragan
Wall rough in ok cover
Electrical Rough-In3/18/20193/19/20193/19/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Steven Ragan
330.30 MC cobale shall not be installed where subject to physical damage. Stand offs required to remove MC from interior of studs