Permit Information
Permit NumberELE19-00943
StatusFinaled
Name M & B ELECTRIC
Site Address 9615 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install power to new sign
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/25/20193/25/20193/25/2019PPASS
DetailsRock A. Hudson
We will not be on jobsite call if there is a problem working close to sign job thanks. Phone #: ###-#### Inspection requested via web by robert feller Final ok
Rough-In Permanent Service3/22/20193/22/20193/22/2019PPASS
DetailsTom Saunders
We will be on site have fault current label there in 1 hour Phone #: ###-#### Inspection requested via web by robert feller...
p/s u/g new ok
Rough-In Permanent Service3/19/20193/20/20193/20/2019AFAIL
DetailsRock A. Hudson
Need service meter inspected for IPCO hookup. There is a strap missing on the 2'''' riser conduit into meter, we will install one when we run the conduits up the sign support column call if there are any problems thanks. Phone #: ###-#### Inspection requested via web by robert feller
110.24- Available fault current shall be posted with value and date calculated prior to permanent service inspection.

408.36(D)- Plug in type over current devices that are back fed shall be secured in place by additional fasteners.
Disregard fastening overcurrent device, reference is for field installed devices not factory installed.
Electrical Rough-In3/18/20193/19/20193/19/2019PPASS
DetailsTom Saunders
We will be digging in the conduit for IPCO starting at 8 am will need an inspection to cover trench, in a busy public area. Phone #: ###-#### Inspection requested via web by robert feller...
informed contractor that verification of depth needs done by IPCO...did verify the depth of 3ft at time for need to backfill-high traffic area
ground rods verified-2 for new service