Final | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | PASS |
Tom Saunders
|
|
|
access 3600 Phone #: ###-#### Inspection requested via web by David Nelson... corrections made ok to final
|
Final | 8/12/2019 | 8/12/2019 | 8/12/2019 | P | FAIL |
Tom Saunders
|
|
|
access 3600 Phone #: ###-#### Inspection requested via web by David Nelson... 1..MOCP on mini split units do not meet manuf rating...exceed 80% of circuit 2..NM cable not rated to be used outside...thhn needed to wire mini split units...all previous units will be reinspected for proper wiring...building 9333 needs addressed
|
Final | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | FAIL |
Tom Saunders
|
|
|
access 3006 Phone #: ###-#### Inspection requested via web by David Nelson...no access doors locked
|
Rough-In Permanent Service | 3/21/2019 | 3/21/2019 | 3/21/2019 | P | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson p/s u/g n ok
|