Permit Information
Permit NumberELE19-01018
StatusFinaled
Name SOUTHERN IDAHO ELECTRIC
Site Address 390 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: electrical for Pad 3 shell
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/26/20197/26/20197/26/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
General contractor foreman stated could not find sign off card when asked. No card posted.
Final ok
Final7/25/20197/25/20197/25/2019PFAIL
DetailsRock A. Hudson
Final for pad 3 Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
314.25- All boxes shall have covers. 3 located in ceiling above panel, 1 ceiling south side.
330.30- MC cable shall be secured with in 12" of a box. Several thru out.
590.6- All 15 and 20 amp 120 volt receptacle outlets installed for power during construction shall have GFCI protection for personel.
Electrical Rough-In7/16/20197/17/20197/16/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
East underground for 6 lights rough in ok cover
Electrical Rough-In7/11/20197/11/20197/11/2019APASS
DetailsRock A. Hudson
exterior canopies Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Areas noted rough in ok cover
Permanent Service5/31/20196/3/20196/3/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
p/s u/g n ok
Electrical Rough-In5/23/20195/24/20195/24/2019APASS
DetailsRock A. Hudson
walls Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Perimeter shell walls rough in ok cover
Electrical Rough-In5/23/20195/23/20195/23/2019PCANC
DetailsRock A. Hudson
Walls Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack Inspection cancelled from web by: Lee VanSchoiack
Electrical Rough-In4/4/20194/4/20194/4/2019APASS
DetailsRock A. Hudson
ug conduit Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Underslab rough in ok cover
Electrical Rough-In3/27/20193/27/20193/27/2019APASS
DetailsRock A. Hudson
ufer Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
Concrete encased electrode rough in ok cover