Final | 4/24/2019 | 4/24/2019 | 4/24/2019 | P | PASS |
Rock A. Hudson
|
|
|
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat Final ok
|
Electrical Rough-In | 4/24/2019 | 4/24/2019 | 4/24/2019 | P | PASS |
Rock A. Hudson
|
|
|
Need grid inspection as well please. Phone #: ###-#### Inspection requested via web by Dean Gernaat Grid rough in ok cover
|
Final | 4/23/2019 | 4/24/2019 | 4/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Grid inspection and electrical final Lock box code 8463 located on the hand rail in stairwell Phone #: ###-#### Inspection requested via web by Dean Gernaat 210.8- All receptacles located with in 6' of break room sink ( when set) shall have GFCI protection. 314.25- All boxes above grid shall have covers installed. Office 1, hallway.
|
Electrical Rough-In | 4/9/2019 | 4/9/2019 | 4/9/2019 | P | PASS |
Rock A. Hudson
|
|
|
Lock box code 8463 located on the hand rail in stairwell. Looking for OK to cover floor box in conference room, and wall in break room. Phone #: ###-#### Inspection requested via web by Dean Gernaat Area noted rough in ok cover
|
Electrical Rough-In | 3/27/2019 | 3/28/2019 | 3/28/2019 | A | PASS |
Tom Saunders
|
|
|
Walls inspection. Lock box code 8463 located on the hand rail in stairwell. Phone #: ###-#### Inspection requested via web by Dean Gernaat... wall cover ok
|