Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-01226
StatusFinaled
Name BOISE ELECTRIC SERVICES
Site Address 303 N 2ND ST
Project NameBaxter Apartment Renovation
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: New 800 amp service. New 200 amp common panel, six new 100Amp panels. Feeders, grounds.new electrical through out. Repull all branch circuits to include grounds and new devices. Installation of owner provided lights.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/13/20206/15/20206/15/2020PPASS
DetailsRock A. Hudson
NOT ON SITE. BACK DOOR OPEN. CALL WITH QUESTIONS. Phone #: ###-#### Inspection requested via web by Garrett Collins No card posted. Final ok
Electrical Rough-In10/29/201910/29/201910/29/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Garrett Collins
Discussed area to right of ranges may have counter top added beyond where receptacle outlets have been roughed in. At final receptacle outlets shall be installed to comply with 210.52(C), would be OK to install at end of cabinet due to pocket door.
Unit 6 rough in ok cover
Electrical Rough-In10/24/201910/25/201910/25/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Garrett Collins
Units 2 and 4 rough in ok cover
Electrical Rough-In10/8/201910/9/201910/9/2019PPASS
DetailsRock A. Hudson
Units one and five Phone #: ###-#### Inspection requested via web by Garrett Collins Units noted rough in ok cover
Electrical Rough-In10/4/201910/7/201910/7/2019PPASS
DetailsRock A. Hudson
On site Phone #: ###-#### Inspection requested via web by Garrett Collins
BLD states only remodelling kitchens and bathrooms in each unit with smokes added. Wall cover not removed in most of units.
Basement lids and unit 3 only rough in ok cover
Electrical Rough-In7/11/20197/11/20197/11/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Garrett Collins
BLD19-02329 is still under review, unable to do inspections until it has been issued.
210.52- Several areas do not comply with receptacle layout of living spaces. Smoke detectors not roughed in. BLD will determine complete scope of work.
Permanent Service4/11/20194/12/20194/12/2019PPASS
DetailsRock A. Hudson
Ok to energize. Neil on site Phone #: ###-#### Inspection requested via web by Garrett Collins
65k rated main, will verify available fault current in future as per 110.9 and 110.24.
p/s o/h rec ok
Conference4/8/20194/8/20194/8/2019PDONE
DetailsRock A. Hudson
Service mast Phone #: ###-#### Inspection requested via web by Garrett Collins
Discussed overhead service entrance clearance from windows. New service mast will be located between windows and from attachment point should clear windows by well over the 3' needed. Will install 2 ground rods and will include metal underground water pipe in future if needed. New panels will be installed in each unit with new house panel, new codes only apply to new work being performed.