Final | 6/4/2019 | 6/5/2019 | 6/5/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
Final | 5/28/2019 | 5/28/2019 | 5/28/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton No lighting changes were made. 210.71- Conference room 215 sq. ft. and larger shall have a floor receptacle installed at least 6' from a wall. 247 sq. ft. measured. Also a conference room shall have the number of receptacles installed as if room was a residential livable room. Once number of receptacles needed has been determined they may be placed at any location owner or tenant wants. 6 minimum needed for conference room.
|
Electrical Rough-In | 4/8/2019 | 4/8/2019 | 4/8/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Wall rough in ok cover.
|