Permit Information
Permit NumberELE19-01351
StatusFinaled
Name CURRENT ELECTRIC COMPANY
Site Address 2454 N MILWAUKEE ST Unit: 110
Project Name 
Customer Number3458
ePlanReviewNo
Description
Addition: tenant improvement in existing building, 200amp service is existing, I am installing plugs, switches and lights
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/26/20196/27/20196/27/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by steve sellers...corrections made..ok to final
Final6/26/20196/26/20196/26/2019AFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by steve sellers...
1) all openings in panel shall be closed
2) all outlets within 6ft of sink/water need GFCI protection...washing stations
3)switch for light and outlet at furnace in attic need added at attic access
Electrical Rough-In4/23/20194/23/20194/23/2019APASS
DetailsTom Saunders
update notes...rough should of been pass not cancel
Electrical Rough-In4/17/20194/17/20194/17/2019ACANC
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by steve sellers...
rough ok to cover