Final | 7/10/2019 | 7/11/2019 | 7/11/2019 | A | PASS |
Eric Story
|
|
|
There will be someone home. If you have any questions please feel free to contact Darren ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Correction fixed final ok
|
Final | 7/9/2019 | 7/10/2019 | 7/10/2019 | A | FAIL |
Eric Story
|
|
|
Lock box code 3380. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 440.6 (a) Shall meet name plate rating of equipment. 20 amp installed on 12 gauge wire and min is 29.7 amps. Larger size wire required
|
Rough-In Permanent Service | 4/26/2019 | 4/29/2019 | 4/29/2019 | A | PASS |
Eric Story
|
|
|
It will be open. If you have any questions please feel free to contact Tony ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Rough-in ok to cover p/s u/g n ok
|