Final | 5/16/2019 | 5/17/2019 | 5/17/2019 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams final ok
|
Permanent Service | 5/15/2019 | 5/16/2019 | 5/15/2019 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams p/s o/h rec ok
|
Final | 5/6/2019 | 5/6/2019 | 5/6/2019 | P | NR |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Not ready for final at this time
|
Permanent Service | 5/6/2019 | 5/6/2019 | 5/6/2019 | P | PART |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jim Williams Emergency power conntection completed over the weekend. 5 working days to start the procees to correct code violations with service panel. NEC 408.38 No Dead front on service panel, NEC 314.17(B) Conductor entering enclosure without abrasion protection. Branch circuit raceway not attached to enclosure. Neutrals and grounds terminated under same lugs. Branch circuits doubled up on circuit breakers.Ocd for A/C unit over sized. update grounding system. Complete directory. Existing service installed without inspection, current NEC applies.
|