Final | 6/10/2019 | 6/11/2019 | 6/11/2019 | A | PASS |
Rock A. Hudson
|
|
|
Corrections were complete. Phone #: ###-#### Inspection requested via web by David Feller Final ok
|
Final | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Final inspection. Phone #: ###-#### Inspection requested via web by David Feller See ceiling rough in inpection.
|
Rough-In Permanent Service | 6/6/2019 | 6/7/2019 | 6/7/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Ceiling cover inspection. Phone #: ###-#### Inspection requested via web by David Feller 210.8- All 15 and 20 amp 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room. 314.25- All boxes shall have covers. Reception and waiting areas. *BLD19-01289 lists break room as being created under this permit and shall be part of scope of work.
|
Electrical Rough-In | 5/13/2019 | 5/15/2019 | 5/15/2019 | A | PASS |
Rock A. Hudson
|
|
|
Wall cover Phone #: ###-#### Inspection requested via web by David Feller Misc walls through out added for dividing wall and offices rough in ok cover
|