Permit Information
Permit NumberELE19-01687
StatusFinaled
Name R M E INC
Site Address 645 E GOWEN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install (2) City of Boise Street Lights
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/10/20197/11/20197/11/2019APASS
DetailsRock A. Hudson
(2) City of Boise Streetlights along Gowen.

Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer
Checked wrong location on previous day.
All complete. Good job. Final ok
Final7/10/20197/10/20197/11/2019PPEND
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tyler Bowen
110.12(B)- Equipment shall not be damaged. In ground junction box damaged on center light pole.
352.46- Where a conduit enters a box or enclosure a bushing or adapter shall be installed to protect conductors from damage. All in ground boxes.
I checked wrong location on 7-10-19. Actual location installation complete and all good.
Electrical Rough-In6/3/20196/4/20196/4/2019APASS
DetailsJames Ady
Not sure if you need to inspect the public works street lights before we pour but i have called them for inspection tomorrow. If you need to see them before concrete also please do so. Thanks Phone #: ###-#### Inspection requested via web by Tyler Bowen This is a Public works project. Did look at underground. OK to cover