Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE19-01961
StatusFinaled
Name COPPERHEAD ELECTRIC
Site Address 100 S 6TH ST
Project NameChina Blue - T.I.
Customer Number 
ePlanReviewNo
Description
Alteration: Electrical modifications to Power & Lighting in first-floor bar area
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/2/20198/2/20198/2/2019PPASS
DetailsRock A. Hudson
Final Phone #: ###-#### Inspection requested via web by Casey Fouts Final ok
Final7/31/20198/1/20198/1/2019PFAIL
DetailsRock A. Hudson
Final inspection invite. Please call me 30min in advance Phone #: ###-#### Inspection requested via web by Casey Fouts
210.8(B)- Main bar area existing plug strip not GFCI protected right of entry to bar. Section to right of GFI.
314.25- All boxes shall have covers. Receptacle above main bar. Expoed MC and no cover on receptacle.
330.12- MC shall not be installed where subject to physical damage. MC exposed in upstairs bar, need wall cover.
406.5- Receptacles shall not be installed face up in counter top spaces. Receptacles located in main bar center counter top shall be installed in a listed box for this application,
Electrical Rough-In6/19/20196/20/20196/20/2019APASS
DetailsRock A. Hudson
1st floor walls. Phone #: ###-#### Inspection requested via web by Casey Fouts
Storage room walls rough in ok cover
Electrical Rough-In6/13/20196/13/20196/13/2019PPASS
DetailsRock A. Hudson
Rough in ceiling 1st floor. Phone #: ###-#### Inspection requested via web by Casey Fouts
Called and had ELE attached to BLD 19-00936.
Ceiling area over sunken floor main bar area only rough in ok cover