Electrical Rough-In | 6/2/2019 | 6/3/2019 | 6/3/2019 | A | PASS |
Eric Story
|
|
|
Corrections have been taken care of Phone #: ###-#### Inspection requested via web by Steve Craig Corrections fixed soffit only ok to cover
|
Electrical Rough-In | 5/30/2019 | 5/30/2019 | 5/30/2019 | P | FAIL |
Eric Story
|
|
|
Recessed can roughin for cover Phone #: ###-#### Inspection requested via web by Steve Craig 1)Unused openings shall be closed 2) Type MC shall be supported within 6' between runs and 12" of a box 3) main run from building has a big nick in wire and needs replaced
|